Skip to the calculator
Rule Calculator

Voltage Drop Calculator

With supply voltage 240 V, load current 20 A, one-way run length 150 ft, voltage drop comes to 7.46 V — voltage dropped. It is reached in 8 steps, the last of which is 2 * 12.9 * 20 * 150 / 10380, and each one is printed on the page with its numbers filled in. The formula is the one published by NFPA 70, not an approximation fitted to it.

Voltage lost along a copper or aluminium run, as volts and as a percentage, against the 3% the NEC recommends for a branch circuit.

Formula and sources checked · How we check

Supply voltage 240 V, Load current 20 A, One-way run length 150 ft, Conductor Copper

7.46 V

Voltage dropped for the example below. Editing a field recomputes the calculator below; this figure holds the answer the page was loaded with.

It is written into the HTML rather than drawn by a script, so a search engine reading this page without running JavaScript still finds an answer.

Voltage dropped
7.46 V
Circular mils
10,380
Resistivity constant K
12.9
Voltage dropped in the run
2 * 12.9 * 20 * 150 / 103807.457 V
Drop as a percentage
7.4566474 / 240 * 1003.107 %
Voltage reaching the load
240 - 7.4566474232.543 V
Power burned in the wire
7.4566474 * 20149.133 W
Longest run that stays under 3%
10380 * 0.03 * 240 / (2 * 12.9 * 20)144.837 ft
Percentage points under the 3% guideline
3 - 3.1069364-0.107 %

Ask about this in the chatCompare: copper against aluminiumVoltage Drop Chart: 10 AWG Copper at 20 A

Worked example

20 A at 240 V down 150 ft of 10 AWG copper loses 7.46 V. That is 3.11% of the supply, just past the 3% the NEC’s informational note recommends: the load sees 232.5 V and 149 W is burned heating the cable. Holding this circuit under 3% means either stopping the run at 145 ft or moving up to 8 AWG.

How to work it out yourself

  1. 1.Measure the run one way. The formula already counts the return conductor on a single-phase circuit, which is where the 2 comes from; three-phase uses 1.732 because the return path is shared.
  2. 2.Size for heat first, then check the drop. Ampacity — how much current the insulation can carry without cooking — is a code requirement; voltage drop is a performance guideline, and it is the one that decides whether a motor at the end of a long run starts properly.
  3. 3.If the drop is over 3%, the fix is a fatter conductor, not a longer one: each step up in AWG size adds roughly 26% more circular mils, and the drop falls in proportion.
  4. 4.Aluminium carries about 60% as well as copper for the same size, so an aluminium run needs two sizes up to match a copper one on drop.
  5. 5.A drop bigger than the supply voltage is the arithmetic telling you the conductor cannot carry that load over that distance at all — the negative figure is not a result, it is the circuit failing. Size up until the drop is a few percent.

Drop along the run, 10 AWG copper at 20 A on 240 V

07.514.925 One-way run length: 1.2 V50 One-way run length: 2.5 V75 One-way run length: 3.7 V100 One-way run length: 5 V150 One-way run length: 7.5 V200 One-way run length: 9.9 V250 One-way run length: 12.4 V300 One-way run length: 14.9 V25300One-way run length (ft)
Drop along the run, 10 AWG copper at 20 A on 240 V
One-way run length (ft)Voltage droppedDrop as a percentageVoltage reaching the load
251.24 V0.52 %238.76 V
502.49 V1.04 %237.51 V
753.73 V1.55 %236.27 V
1004.97 V2.07 %235.03 V
1507.46 V3.11 %232.54 V
2009.94 V4.14 %230.06 V
25012.43 V5.18 %227.57 V
30014.91 V6.21 %225.09 V

The drop is linear in length: double the run, double the loss.

The formula

  1. Circular mils
  2. Resistivity constant K
  3. Voltage dropped in the run2 * 12.9 * 20 * 150 / 10380
  4. Drop as a percentage7.4566474 / 240 * 100
  5. Voltage reaching the load240 - 7.4566474
  6. Power burned in the wire7.4566474 * 20
  7. Longest run that stays under 3%10380 * 0.03 * 240 / (2 * 12.9 * 20)
  8. Percentage points under the 3% guideline3 - 3.1069364

Source: NFPA 70 — National Electrical Code (free online access), Copper Development Association — ampacity adjustments for wire and cable

Questions people actually ask

Does the NEC require voltage drop under 3%?
No. The 3% figure for a branch circuit, and 5% for feeder and branch combined, appear in informational notes — 210.19(A) and 215.2(A) — which are recommendations rather than enforceable rules. Some local amendments and some load types do make it mandatory, and equipment manufacturers often specify their own limit.
What is the voltage drop formula?
VD = 2 × K × I × L ÷ CM for single-phase, and 1.732 × K × I × L ÷ CM for three-phase, where K is 12.9 for copper or 21.2 for aluminium, I is amps, L is the one-way run in feet and CM is the conductor’s circular mils. It is a resistance calculation with the round trip built into the 2.
Why does a long run make lights dim and motors struggle?
Because the wire is a resistor. Every volt lost along it is a volt the load never sees, and the power that vanishes — 149 watts on the run above — heats the cable instead. Motors are the worst affected: torque falls with the square of voltage, so a 5% drop costs about 10% of starting torque.
Should I use the 75°C or 90°C column?
Neither changes this calculation. K = 12.9 is copper at about 75°C, which is the normal working assumption; a conductor running hotter has slightly higher resistance and drops slightly more, and a cold run drops slightly less. Ampacity, not drop, is what the temperature columns are for.

Related

Where this one stops

Put this calculator on your site

Free, no attribution required beyond the link.

<iframe src="https://rulecalculators.com/embed/voltage-drop" width="100%" height="420" style="border:1px solid #e7e4de;border-radius:12px" title="Voltage Drop Calculator"></iframe>
Did this answer your question?