Skip to the calculator
Rule Calculator

kW and kVA to Amps

With rating 10 kW or kVA, voltage 400 V, power factor 0.8, kw and kva to amps comes to 18.0 A — amps. It is reached in 4 steps, the last of which is 12.5 * 1000 / (400 * 1.7320508), and each one is printed on the page with its numbers filled in. The formula is the one published by IEEE Std 141, not an approximation fitted to it.

Current drawn by a load rated in kW or kVA, on any voltage and phase. The unit on the nameplate decides whether power factor enters the sum.

Formula and sources checked · How we check

Nameplate is in kW — real power, Rating 10 kW or kVA, Voltage 400 V, Supply AC three phase — line-to-line voltage

18.0 A

Amps for the example below. Editing a field recomputes the calculator below; this figure holds the answer the page was loaded with.

It is written into the HTML rather than drawn by a script, so a search engine reading this page without running JavaScript still finds an answer.

Amps
18.0 A
Apparent power
0 * 10 + 1 * (10 / 0.8)12.5 kVA
Real power
1 * 10 + 0 * (10 * 0.8)10 kW
Current
12.5 * 1000 / (400 * 1.7320508)18.042 A
Reactive power
sqrt(abs(12.5 * 12.5 - 10 * 10))7.5 kVAr

Ask about this in the chat

Worked example

A 10 kW three-phase motor at 0.8 power factor draws 18.0 A, not the 14.4 A a power-factor-free sum gives. The extra 25% is reactive current the motor returns to the supply every cycle and the cable still has to carry.

How to work it out yourself

  1. 1.Read the nameplate unit before anything else. kW is real power and kVA is apparent power, and confusing them is a 25% error at a typical power factor — always in the direction of undersizing.
  2. 2.Use the line-to-line voltage for three phase. That is what a plate marked 400 V or 480 V means; the line-to-neutral 230 V or 277 V is a different number and gives an answer √3 too large.
  3. 3.Take the power factor from the nameplate where there is one. Generator sets are rated at 0.8 by convention, so a 100 kVA set is an 80 kW set.
  4. 4.The reactive line is what a capacitor bank would have to supply to correct the load to unity — the size of the correction problem, in kVAr.

Generator kVA to amps, 400 V three phase

090.2180.45 Rating: 9 A7.5 Rating: 13.5 A10 Rating: 18 A15 Rating: 27.1 A20 Rating: 36.1 A30 Rating: 54.1 A40 Rating: 72.2 A50 Rating: 90.2 A60 Rating: 108.3 A75 Rating: 135.3 A100 Rating: 180.4 A5100Rating (kW or kVA)
Generator kVA to amps, 400 V three phase
Rating (kW or kVA)AmpsReal power
59.0 A5 kW
7.513.5 A7.5 kW
1018.0 A10 kW
1527.1 A15 kW
2036.1 A20 kW
3054.1 A30 kW
4072.2 A40 kW
5090.2 A50 kW
60108.3 A60 kW
75135.3 A75 kW
100180.4 A100 kW

Generators are rated in kVA at a power factor of 0.8, so the usable real power is 80% of the plate figure: a 100 kVA set delivers 80 kW.

The formula

  1. Apparent power0 * 10 + 1 * (10 / 0.8)
  2. Real power1 * 10 + 0 * (10 * 0.8)
  3. Current12.5 * 1000 / (400 * 1.7320508)
  4. Reactive powersqrt(abs(12.5 * 12.5 - 10 * 10))

Source: IEEE Std 141 — three-phase power relationships, 10 CFR 431 Subpart B — federal efficiency standards and nameplate data for electric motors, NFPA 70 (NEC) Article 430 — motor circuit conductors and full-load current tables

Questions people actually ask

How do you convert kW to amps on three phase?
Amps = kW × 1000 ÷ (volts × power factor × 1.732). At 400 V and 0.8 PF, 10 kW is 18.0 A. Leaving the power factor out gives 14.4 A and undersizes the cable by a quarter.
What is the difference between kW and kVA?
kVA is what the supply carries, kW is what the load converts to work. They are equal only at a power factor of 1. A generator rated 100 kVA at 0.8 PF delivers 80 kW, and connecting an 100 kW load to it overloads the alternator even though the "power" figures look compatible.
Why are generators rated in kVA?
Because the alternator windings and the cabling are limited by current, and current follows apparent power. The engine is limited by real power. Rating the set in kVA at an assumed 0.8 power factor states the electrical limit, which is the one that burns something out.
What is kVAr?
Reactive power — the part that shuttles between the supply and the load's magnetic fields without doing work. It is the third side of the triangle: kVA² = kW² + kVAr². Utilities charge large customers for it, and a capacitor bank sized in kVAr is how it is cancelled.
Is motor full-load current the same as this?
Close, but the NEC requires conductors to be sized from the tables in Article 430 rather than from a nameplate calculation. Those table values are deliberately conservative. Use this for sizing decisions and the code tables for anything being inspected.

Related

Put this calculator on your site

Free, no attribution required beyond the link.

<iframe src="https://rulecalculators.com/embed/kw-to-amps" width="100%" height="420" style="border:1px solid #e7e4de;border-radius:12px" title="kW and kVA to Amps"></iframe>
Did this answer your question?