Voltage Drop Chart: 10 AWG Copper at 20 A

Voltage lost every 25 feet on a 240 V single-phase circuit in 10 AWG copper carrying 20 A, with the percentage and the voltage still reaching the load. The 3% guideline is crossed at 145 feet on this circuit; read down to your run length, or change the wire size on the calculator to move the line.

Source data and formula checked · How we check

Voltage Drop Chart: 10 AWG Copper at 20 A reads voltage dropped straight off one-way run length, for 19 values from 25 to 800. Every row is computed from the same formula the calculator uses, not measured or copied from another table, so a value between two rows can be worked out the same way. The formula is the one published by NFPA 70.

One-way run length in feet. Every figure doubles the distance internally for the return conductor.

Questions people actually ask

How do I read the Voltage Drop Chart: 10 AWG Copper at 20 A?
Find your one-way run length in the first column and read across. At 25 ft the voltage dropped is 1.24 V; at 800 ft it is 39.77 V. The table runs from 25 ft to 800 ft in 19 rows.
How much does the voltage dropped change per row?
By 1.24 V for every 25 ft of one-way run length, and by the same amount everywhere in the table — the relationship is a straight line, so halfway between two rows is halfway between their two answers. That is what makes reading between the rows safe here.
What if my one-way run length is outside the table?
The chart covers 25 ft to 800 ft, which is the range people actually look up. Anything above or below goes into the calculator, which takes any figure and shows each step of the working rather than only the result. Open the voltage drop calculator.
Where do these numbers come from?
Every row is computed at build time from the formula published by NFPA 70, by the same code behind the calculator — not transcribed from another table, which is how a rounding error in one chart ends up in twenty.
19 rows

Need a different number?

The chart covers the common values. For anything between the rows, the voltage drop calculator takes any figure and shows the working.

Source: NFPA 70 — National Electrical Code (free online access), Copper Development Association — ampacity adjustments for wire and cable